Battery Charger Output Contactor (Aux)

Battery charger output contactor (Aux)

The purpose of the Auxiliary Battery Charger Output Contactor is to connect and isolate the auxiliary battery starting from its charger. In the battery charger unit, you typically need two normally open pole contactors.

We offer a wide variety of designs to fit most installation requirements.

  • Compact size
  • High reliability
Image Image Image Image
Series
Size
Poles
LTC
100
2NO*

LTCS
250
2NO*

LTCS
300
2NO*

LTHS
320
2NO*

Rated Operational Voltage
(up to)
[V] 900 1800 1800 1800
Thermal Current @ 75°C [A] 80 200 270 320
Short Circuit Withstand Current for 5ms [kA] 1.5 5 5 8
Fault Making Capacity [kA] 0.9 2.4 2.4 4.8
DC Rated Operational Current (L/R=15 ms) 440 Vdc [A] 72 - - -
DC Max Breaking Current (L/R=5 ms) 440 Vdc [A] 100 - - -
Dimensions Length L [mm] 120 140 157 221
Width W [mm] 99 110 109 114
Height H [mm] 154 157 140 301
Weight [kg] 2 3.1 3.3 8.5

* Series connected