Main DC Circuit Breaker

Main DC Circuit Breaker

DC Circuit Breakers protect propulsion and auxiliary high-voltage circuits from short circuits. A DC Circuit Breakers with a high breaking capability must be coordinated with the DC substation short-circuit protections when short circuits occur close to a substation.

We provide a wide and flexible range of products fitting most installation requirements.

  • High electrical durability guaranteed with ceramic arc-chute
  • Intrinsic safe device thanks to magnetic latch
Image Image Image Image Image Image Image
Series
Size
Archute


IR3000V
3015 | 3030
09LP

IR3000V
3015 | 3030
09MP

IR3000V
3015 | 3030
18MP

IR4000VH
4030 | 4045
18MP

IR4000VV
4030 | 4045
18MP

IR4000VH
4030 | 4045
36MP

IR4000VV
4030 | 4045
36M

Rated Operational Voltage [V] 900 900 1800 1800 1800 3600 3600
Thermal Current Ith(A)= @ 40°C [A] 1500 | 3000 1500 | 3000 1500 | 3000 3000 | 4500 3000 | 4500 3000 | 4500 3000 | 4500
Rated Short Circuit Making and Breaking Capacities
T1 [kA/ms] 30/0
(42kA Peak)
50/0
(70kA Peak)
30/0
(42kA Peak)
100/0
(140kA Peak)
100/0
(140kA Peak)
55/0
(77kA Peak)
55/0
(77kA Peak)
T2 [kA/ms] 30/15 32.5/15 30/15 60/15 60/15 50/15 50/15
T3 [kA/ms] 30/50 30/50 30/40 50/40 50/40 50/30 50/30
T4 [kA/ms] 30/150 30/150 30/100 35/100 35/100 50/50 50/50
Dimensions Length L [mm] 548 548 548 1240 679 1240 679
Width W [mm] 395 475 475 322 916 322 916
Height H [mm] 265 265 265 700 319 700 319
Weight [kg] 44 54 54 173 | 180 173 | 180 205 | 210 205 | 210