Load Break Switch

Load Break Switch

In a circuit with two rail section lines fed by two independent feeder breakers, service continuity must be guaranteed when one of the feeder breakers requires maintenance. A Load Break Switch can bypass the out-of-service feeder breaker to prevent power outage.

This function can be covered by an interconnect circuit breaker, recommended for best performance, or by an underload switch disconnector, cheaper but missing any protections.

  • High making capacity
  • High short-circuit withstand capacity (interconnect circuit breaker)
  • High reliability
Series MLBS
Rated Operational Voltage [V] 750 1500 3000
Rated Service Current (Ine) [A] 1000 | 2000 | 3000 | 4000 1000 | 2000 | 3000 | 4000 1000 | 2000 | 3000 | 4000
Component Category (EN50125-3, table 1) III | VI III | VI III | VI
Maximum Breaking Capacity (EN50125-3, tab. 1) [A] INe | 3INe INe | 3INe INe | 3INe
Rated Short Time Withstand Current [kA/ms] 75/250 75/250 75/250
Short-Circuit Current Peak [kA] 100 100 100
Making Capacity Current [kA] 100 100 100
Dimensions Length L [mm] 1060 1060 1060
Width W [mm] 597 597 597
Height H [mm] 878 878 878